Process Technology Logo

Distributed by:

CDI Equipment Division logo

Equipment Overview | Filter Pump Industries / Penguin Pump | Process Technology

 

Conductivity Type Liquid Level Controls: LC Series

Conductivity Type Liquid Level Controls: LC Series

Single Level Control - 2 Probes

Model Number Probe Length
(Field Trim)
In./(mm)
Probe Shipping Weight
Lb./(Kg)
2 ( * ) 6 6 (155) 3 (1.5)
2 ( * ) 12 12 (305) 3 (1.5)
2 ( * ) 18 18 (460) 4 (2)
2 ( * ) 24 24 (610) 6 (2.5)
2 ( * ) 30 30 (762) 7 (3)
2 ( * ) 36 36 (915) 8 (3.5)
2 ( * ) 48 48 (1220) 9 (4)

Two Level Control - 3 Probes

Model Number Probe Length
(Field Trim)
In./(mm)
Probe Shipping Weight
Lb./(Kg)
3 ( * ) 6 6 (155) 3 (1.5)
3 ( * ) 12 12 (305) 3 (1.5)
3 ( * ) 18 18 (460) 4 (2)
3 ( * ) 24 24 (610) 6 (2.5)
3 ( * ) 30 30 (762) 7 (3)
3 ( * ) 36 36 (915) 8 (3.5)
3 ( * ) 48 48 (1220) 9 (4)

COMPONENTS PURCHASED SEPARATELY - SPECIFY PROBE MATERIAL:
  • S=Stainless Steel.
  • H=Hastelloy C®.
  • T=Titanium.
  • G=Graphite-tipped
  • Fluoropolymer (PTFE) covered standard

IMPROVES PROCESS CONTROL:
  • Provides automated control and consistent liquid levels in most conductive aqueous processes, waste treatment tanks and when leak detection is required.
  • Adds protection against fires and tank damage associated with low-level conditions.
  • Dual probe units (LC2): for single point control.
  • Multi probe units (LC3): for two-point control and refill/pump down applications.

CORROSION RESISTANT PROBES:
  • Fluoropolymer (PTFE) covered: 316 stainless steel, titanium, Hastelloy C® and graphite tipped Hastelloy probe materials.
  • Lengths: up to 48 inches (1220mm) standard.
  • Field trimmable (except graphite probes).

CORROSION RESISTANT ENCLOSURES:
  • Control enclosure: gasketed UL Type 4/4x, IP62 (indoor) polypropylene box with stainless steel hardware.
  • Probe enclosure: vapor resistant polypropylene head with 10-foot (3m) flexible lead and quick connect plug for easy connection to remote circuitry.

CERTIFICATIONS:
  • cULus and CE.

CAPACITIES:
  • Relay rating: 10-amps at 120/208 to 240 volts, 50/60 Hz, single pole, double throw.
  • Sensing output: 14.5 VAC.
  • Ambient temperature range: 0°F (-18°C) to 104°F (40°C).
  • Maximum solution resistance: 70,000 ohm-CM.
  • Single phase only.

SAFETY FEATURES:
  • Ground connection on circuit board.
  • Minimal AC sensing current has no affect on plating processes.

CONSULT FACTORY FOR THE FOLLOWING OPTIONS:
  • Probe lengths up to 20-foot (6m).
  • Can be pre-wired into combination controls.
  • Fluid stilling chambers.
  • Longer flexible cords.
  • Cord extensions for existing units.
  • 4, 5 or 6-probe devices for multiple level control applications.

NOTE:
  • Do not use in flammable solutions or in the presence of flammable gases. Not for use in deionized water, oil or other non-conductive solutions.

Downloads: